AXLJ TT 36 kV 1x240/35

Description

Description

Standards

  • National
    SS 424 14 16

AXLJ TT is a longitudinally and radial watertight, XLPE-insulated, copper wire screened, PE sheathed 1-core cable with circular aluminium conductor. The cable is designed according to HD 620. The conductor has resistance and number of wires according to IEC 60228 class 2. The sheath is marked type/manufacturer/year+month/metre marking. AXLJ TT is not flame retardant.

 

The following applies if presstools are used:

The actual copperscreen are one cross section lower than the typemarking. This means that if the screen is 25 mm² the connector should be 16 mm².

 

Lifemark(TM) recycling marking

The external surface of the outer sheath is embossed with a text which specifies all components in the polymers and prepares the cable for future recycling.

Standards

The cable is in appliable parts constructed according to HD 620.5-K. The cable can be loaded according to SS 424 14 16.

Quality system

Designed, manufactured and tested in accordance with ISO 9001.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Round, stranded
Insulation
XLPE (chemical)
Outer sheath
PE
Colour
Black
Halogen free
Yes
Screen
Copper wires / 6mm²

Dimensional characteristics

Dimensional characteristics

Number of cores
1
Conductor cross-section
240 mm²
Approximate weight
228.0 kg/100m
Conductor diameter
18.2 mm
Screen section
35 mm²
Average sheath thickness
2.3 mm
Nominal outer diameter
49.0 mm
Nominal insulation thickness
8.0 mm

Electrical characteristics

Electrical characteristics

Approx. inductance, trefoil formation
0.38 mH/km
Earth leakage current at 30 kV
- A/km
Max. DC resistance of the conductor at 20°C
0.125 Ohm/km
Nominal phase capacitance
0.21 µF / km
Operating voltage
36 kV
Rated Voltage Uo/U
19/33kV
Resistance of the screen
- Ohm/km

Mechanical characteristics

Mechanical characteristics

Permissible pulling forces
- kN/mm²

Usage characteristics

Usage characteristics

Minimum installation temperature
-20 °C
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Water proof
Longitudinal & radial
Bending factor when installed
8 (xD)
Bending factor when laying
12 (xD)
Length
500 m
Packaging
Drum
Rip cord
Yes

Resources

Resources

Selling & delivery Information

The drum is marked with manufacturer, type of cable and length. The ends of the cable are sealed.

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close